The system tags are a "Read-only" item. Any solutions on how to write/test these tags ?

Is there a way to test the system tags of the PLC ? (The devices have no connection the actual physical devices) I've the "._System._error" tag connected to a SCADA and wanted to display the tag to show some sort of lifesign to the device.

 

Regards,  

 

Jul 24, 2023 12:20 PM UTC

I've went in to quick client and used the enabled system tag. The simulated tag needs to be On too. 

4 replies

Jul 20, 2023 4:19 PM UTC

There is a Channel.device._System._Error that will tell you when Kepware can’t see the PLC anymore.

Jul 21, 2023 9:48 AM UTC

Would there be a way to simulate the ._System.Error tag without the physical device being present ?

 

Jul 21, 2023 7:39 PM UTC
The quick Client maybe? You can put those On and Off Scan...