Alert When Modbus TCP Device Goes Offline

Is there a way to send out alerts from Kepware whenever a connected Modbus TCP/IP device disconnects?

For example, when these errors are shown:

JT_10361438_0-1676039858447.png

Thank you!

rjanardanAnswer
Feb 10, 2023 4:19 PM UTC

You should look into the _Error tag from the _System tag group of the device. 

2 replies

rjanardanAnswer
Feb 10, 2023 4:19 PM UTC

You should look into the _Error tag from the _System tag group of the device. 

Jimmy_TAuthor
Feb 10, 2023 9:13 PM UTC

I like this approach.

We are going to use the Advanced IoT Plugin to scan the "_System._Error" device tags.

If they are true, then there is a disconnection. If they are false, everything is working fine.

 

Thanks!